  6. 3M™ Cold Shrink QT-III Termination Kit 7656-S-4-TI with Top Insulator, JCN Cable, Skirted, 5-25/28 kV, 1.53-2.32 in (38.9-58.9 mm) Cable Insul. O.D., 1 termination/kit

3M™ Cold Shrink QT-III Termination Kit 7656-S-4-TI with Top Insulator, JCN Cable, Skirted, 5-25/28 kV, 1.53-2.32 in (38.9-58.9 mm) Cable Insul. O.D., 1 termination/kit

  • Part Number 7656-S-4-TI
  • 3M ID 7100164705

Provides a void-free seal to jacketed concentric neutral and concentric neutral power cables

High dielectric-constant material regulates the distribution of electric field stress

Suitable for outdoor applications

View more details

Details

Highlights
  • Provides a void-free seal to jacketed concentric neutral and concentric neutral power cables
  • High dielectric-constant material regulates the distribution of electric field stress
  • Suitable for outdoor applications
  • Termination has 1.53 to 2.32-in insulation O.D., 1.84 to 2.80-in jacket O.D. and 0.60 to 2.80-in connector/drop wire O.D
  • Accommodates wire sizes of 1750 to 2000 kcmil at 5kV, 1500 to 2000 kcmil at 8 kV, 1250 to 2000 kcmil at 15kV, 900 to 1750 kcmil at 25/28 kV
  • Integrated jumper wire-top insulator and step-core design allow for easier installation, while sealing compounds provide constant radial pressure
  • Withstands voltages of 5 to 25/28 kV and is 150 kV BIL-rated
  • Includes a 4-skirt, cold shrink termination

3M™ Cold Shrink QT-III 7640-S & 7650-S Series Termination Kit includes a skirted termination with a jumper wire-top insulator. It ensures a pliable, tight seal for jacketed concentric neutral and concentric neutral power cables. The conjunction of high dielectric-constant material and sealing compounds allows the termination to withstand voltages of 5 to 25/28 kV.

3M™ Cold Shrink QT-III 7640-S & 7650-S Series Termination Kit is designed for terminating medium voltage cables. The UV stable, erosion and track-resistant, silicone rubber construction makes the termination suitable for outdoor applications. The lower surface stress, high dielectric-constant material offers an optimized BIL performance while ensuring a leak-proof, compact fit. A jumper wire-top insulator provided on the detachable core allows for convenient installation while offering optimal protection of a circuit from corrosion and animal damages.

Conductor Size Range for
· 5 kV: 1750-2000 kcmil
· 8 kV: 1500-2000 kcmil
· 15 kV: 1250-2000 kcmil
· 25/28 kV: 900-1750 kcmil

This termination is compatible with the following lugs:
QL2-A-1000-1250, for conductor range: 1250 kcmil (15kV), 1000-1250 kcmil (25/28kV)