1. Singapore
  2. All 3M Products
  3. Electrical
  4. Power Cable Connectors
  5. Power Cable Terminations
  6. 3M™ Cold Shrink QT-II Outdoor Termination Kit 5601-4/0, CN cable, 5-15 kV, 0.637-1.12 in (16-28 mm) Cable Insul. O.D., 1 termination/kit

3M™ Cold Shrink QT-II Outdoor Termination Kit 5601-4/0, CN cable, 5-15 kV, 0.637-1.12 in (16-28 mm) Cable Insul. O.D., 1 termination/kit

  • Part Number 5601-4/0
  • 3M ID 7100164233

Provides a void-free seal to concentric neutral cables

High dielectric-constant material regulates the distribution of electric field stress

Suitable for outdoor applications

View more details

Details

Highlights
  • Provides a void-free seal to concentric neutral cables
  • High dielectric-constant material regulates the distribution of electric field stress
  • Suitable for outdoor applications
  • Termination has 0.64 to 1.12-in insulation O.D
  • Accommodates wire sizes of 4/0 AWG at 5kV 100%, 4/0 AWG at 5kV 133%/8 kV 100%, 4/0 AWG at 8 kV 133%, 4/0 AWG at 15kV
  • Molded, silicone rubber insulation offers durability and reduces leakage currents in damp conditions
  • Withstands voltages of 5 to 15kV and is 110 kV BIL-rated
  • Includes a 4-skirt, 1-piece, cold shrink termination and an SC0040 stem connector
  • IEEE Standard 48 Approved for Class 1 terminations

3M™ Cold Shrink QT-II 5600 & 5680 Series Termination Kit includes a 4-skirt, 1-piece termination. It ensures a pliable, tight seal for concentric neutral cables. The conjunction of high dielectric-constant material and silicone rubber insulation allows the termination to withstand voltages of 5 to 15kV.

3M™ Cold Shrink QT-II 5600 & 5680 Series Termination Kit is designed for terminating medium voltage cables in outdoor applications. When this 4-skirt, non-jacketed terminal's core is unwound, it shrinks over the cable and ensures a leak-proof, ideal fit. The track-resistant, silicone rubber insulation of the termination has a hydrophobic property and offers a long-lasting service life while minimizing leakage currents in wet conditions. IEEE Standard 48 Approved for Class 1 terminations.

Conductor Size Range for
· 5 kV (100%): 3/0 AWG-500 kcmil
· 5 kV (133%): 2/0 AWG-500 kcmil
· 8 kV (100%): 2/0 AWG-500 kcmil
· 8 kV (133%):1/0 AWG-350 kcmil
· 15 kV: 4/0 AWG

Typical Properties

Additional Kit Contents

(1) SC0040 Stem Connector

BIL

110 kV

Brands

3M™

Breakout Boot

No

Cable Insulation Outside Diameter Range (metric)

16.3 to 28.4 mm

Cable Shielding

Concentric Neutral (CN)

Case Quantity

1

Indoor/Outdoor

Outdoor Skirted

Insulation Level

100%, 133%

Insulation Outer Diameter (Metric)

16.256 mm, 16.51 mm, 16.764 mm, 17.018 mm, 17.272 mm, 17.526 mm, 17.78 mm, 18.034 mm, 18.288 mm, 18.542 mm, 18.796 mm, 19.05 mm, 19.304 mm, 19.558 mm, 19.812 mm, 20.066 mm, 20.32 mm, 20.574 mm, 20.828 mm, 21.082 mm, 21.336 mm, 21.59 mm, 21.844 mm, 22.098 mm, 22.352 mm, 22.606 mm, 22.86 mm, 23.114 mm, 23.368 mm, 23.622 mm, 23.876 mm, 24.13 mm, 24.384 mm, 24.638 mm, 24.892 mm, 25.146 mm, 25.4 mm, 25.654 mm, 25.908 mm, 26.162 mm, 26.416 mm, 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm

Insulation Rejacketing

No

Lug/Stem Connector Included in Kit

Yes

Number of Conductors

1

Number of Skirts

4

Product Series

5600

Voltage

5 kV, 8 kV, 15 kV

Manufacturing Origin: USA

The designation that a product is Manufactured in the USA means the product undergoes substantial transformation in one of our U.S. Manufacturing plants. Some products contain imported components.

Note: 3M products offered on a government contract that require country of origin representation must be certified by 3M Trade Compliance. Contact customer service at 800-245-3573 to request a certificate.