  6. 3M™ Cold Shrink QT-II Outdoor Termination Kit 5651-2, JCN Cable, 15-25/28 kV, 0.637-1.12 in (16-28 mm) Cable Insul. O.D., 1 termination/kit

3M™ Cold Shrink QT-II Outdoor Termination Kit 5651-2, JCN Cable, 15-25/28 kV, 0.637-1.12 in (16-28 mm) Cable Insul. O.D., 1 termination/kit

  • Part Number 5651-2
  • 3M ID 7100164320

Provides a void-free seal to jacketed concentric neutral power cables

High dielectric-constant material regulates the distribution of electric field stress

Suitable for outdoor applications

View more details

Details

Highlights
  • Provides a void-free seal to jacketed concentric neutral power cables
  • High dielectric-constant material regulates the distribution of electric field stress
  • Suitable for outdoor applications
  • Termination has 0.64 to 1.12-in insulation O.D. and 0.93 to 1.35-in cable jacket O.D
  • Accommodates wire sizes of 2 AWG at 15kV and 2 AWG at 25/28 kV
  • Molded, silicone rubber insulation offers durability and reduces leakage currents in damp conditions
  • Withstands voltages of 15 to 25/28 kV and is 150 kV BIL-rated
  • Includes a 6-skirt, 1-piece, cold shrink termination and an SC0001 stem connector
  • IEEE Standard 48 Approved for Class 1 terminations

3M™ Cold Shrink QT-II 5640 & 5650 Series Termination Kit includes a 6-skirt, 1-piece termination. It ensures a pliable, tight seal for jacketed concentric neutral power cables. The conjunction of high dielectric-constant material and silicone rubber insulation allows the termination to withstand voltages of 15 to 25/28 kV.

3M™ Cold Shrink QT-II 5640 & 5650 Series Termination Kit is designed for terminating medium voltage cables in outdoor applications. When this 6-skirt terminal's core is unwound, it shrinks over the cable and ensures a leak-proof, ideal fit. The track-resistant, silicone rubber insulation of the termination has a hydrophobic property and offers a long-lasting service life while minimizing leakage currents in wet conditions. IEEE Standard 48 Approved for Class 1 terminations.

Conductor Size Range for
· 15 kV: 2 AWG
· 25/28 kV: 2 AWG

Typical Properties

Additional Kit Contents

(1) SC0001 Stem Connector

Application

Cable Termination

BIL

150 kV

Brands

3M™

Breakout Boot

No

Cable Insulation Outside Diameter Range (metric)

16.3 to 28.4 mm

Cable Shielding

Jacketed Concentric Neutral (JCN)

Case Quantity

1

Dielectric Strength (V/mil)

507 V/mil

Indoor/Outdoor

Outdoor Skirted

Insulation Level

100%, 133%

Insulation Outer Diameter (Metric)

16.256 mm, 16.51 mm, 16.764 mm, 17.018 mm, 17.272 mm, 17.526 mm, 17.78 mm, 18.034 mm, 18.288 mm, 18.542 mm, 18.796 mm, 19.05 mm, 19.304 mm, 19.558 mm, 19.812 mm, 20.066 mm, 20.32 mm, 20.574 mm, 20.828 mm, 21.082 mm, 21.336 mm, 21.59 mm, 21.844 mm, 22.098 mm, 22.352 mm, 22.606 mm, 22.86 mm, 23.114 mm, 23.368 mm, 23.622 mm, 23.876 mm, 24.13 mm, 24.384 mm, 24.638 mm, 24.892 mm, 25.146 mm, 25.4 mm, 25.654 mm, 25.908 mm, 26.162 mm, 26.416 mm, 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm

Insulation Rejacketing

No

Jacket Outside Diameter Range (metric)

23.6-34.3 mm

Lug/Stem Connector Included in Kit

Yes

Material

Silicone Rubber

Number of Conductors

1

Number of Skirts

6

Product Color

Grey

Product Series

5650

Voltage

15 kV, 25/28 kV

Manufacturing Origin: USA

The designation that a product is Manufactured in the USA means the product undergoes substantial transformation in one of our U.S. Manufacturing plants. Some products contain imported components.

Note: 3M products offered on a government contract that require country of origin representation must be certified by 3M Trade Compliance. Contact customer service at 800-245-3573 to request a certificate.